Model: | - |
---|---|
Brand: | - |
Origin: | Made In China |
Category: | Electronics & Electricity / Optical Fiber, Cable & Wire / Other Wire & Cable |
Label: | cables , control cable , insulation cable |
Price: |
-
|
Min. Order: | - |
Last Online:28 Feb, 2013 |
XLPE Insulation Control cable
It is used in controlling ,supervising loop and protecting circuit cases of A.C. rated voltage 450/750V or lower .
Executive standard : GB/T 9330-2008
Working Condition
1: Long-term working temperature allowed by cable conductor is 90℃.
2: Environment temperature for installation should be no less than 0℃, allowed bending radius is stipulated as follows : It should be no less than 8 times that of cable OD for unarmored cable ;It should be no less than 12 times that of cable OD for armored .
Codes Meaning
Series code...............................................................................K
Material Code
Copper conductor.....................................................................omitted
XLPE or crosslinked polyolefine insulation................................YJ
PVC sheath ..............................................................................V
PE or Polyolefine sheath...........................................................Y
Classified by Structure and Performance
Braided shielding ......................................................................P
Copper tape shielding ..............................................................P2
Soft structure............................................................................R
Aluminum-polyester tape shieding ...........................................P3
Dual steel tape armor...............................................................2
Steel wire armored...................................................................3
Type and Description
Table 1
Type |
Description |
KYJV |
Control cable with Cu core, XLPE insulation, PVC sheath |
KYJVP |
Control cable with Cu core, XLPE insulation,PVC sheath, copper wire braided shielding |
KYJVP2 |
Control cable with Cu core,XLPE insulation,PVC sheath ,copper tape shielding |
KYJVP3 |
Control cable with copper conductor,XLPE insulation,PVC sheath,aluminum-polyester tape shielding |
KYJV22 |
Control cable with Cu core, XLPE insulation,PVC sheath ,steel tape armor |
KYJVP2-22 |
Control cable with Cu core,XLPE insulation,PVC sheath,copper tape shielding ,steel tape armor |
KYJV32 |
Control cable with Cu conductor ,XLPE insulation,PVC sheath and steel wire armored |
Prefix ZA-、ZB-、ZC- is added to the original type for indication of flame resistance cable ,for example,ZA-KYJV.
We also produce unlisted type of cables as required ,such as KYJVP2-23,KYJY33 and so on .
Technical Parameter
DC resistance of finished cable conductor at 20℃ in table 2
ltem |
unit |
Technical indices |
|||||||
DC resistance of conductor at 20℃ |
Ω/km |
cross section area mm2 |
0.75 |
1.0 |
1.5 |
2.5 |
4 |
6 |
10 |
Category A,B |
24.5 |
18.1 |
12.1 |
7.41 |
4.61 |
3.08 |
1.83 |
||
Category R |
26.0 |
19.5 |
13.3 |
7.98 |
/ |
/ |
/ |
2: Finished cable should bear A.C.voltage of 3.0 KV under power frequency for 5min without puncture of insulation.
DC resistance of finished cable conductor at 90℃in table 3
ltem |
unit |
Technical indices |
|||||||
DC resistance of conductor at 90℃ |
Ω/km |
cross section area mm2 |
0.75 |
1.0 |
1.5 |
2.5 |
4 |
6 |
10 |
Category A |
1.20 |
1.10 |
1.10 |
1.0 |
0.85 |
0.70 |
/ |
||
Category B |
1.4 |
1.30 |
1.0 |
0.90 |
0.77 |
0.65 |
0.65 |
4: Control cable with XLPE insulation has good features of heat resistance, freezing resistance, chemistry resistance ,insulated resistance and long lifetime compared with control cable with PVC insulation.