Product Description
ELECTRICAL RATINGS(3PHASE) SYMMETRICAL BASIS |
1.Rated Frequency |
50/60Hz |
2.Rated Maximum Line to Line Voltage |
12kV,r.m.s |
3.Rated Power Frequency Withstand Voltage:Air
|
48kV,r.m.s |
4.Rated Impulse Withstand Voltage:Air |
95kV,Peak |
5.Rated Normal Current |
2000A |
6.Rated Short-Circuit Current(3Phase Symmetrical Basis) |
40kA,r.m.s |
7.Percentage D.C. Component of Rated S.C. Breaking Current |
50% |
8.Rated Short-Circuit Making Current |
100kA,Peak |
9.Rated Duration of Short Time Current |
3s |
10.Rated Short Time Withstand Current |
40kA,r.m.s |
11.Rated Peak Withstand Current |
100kA,r.m.s |
12.Maximum Contact Resistance at Minimum Closing Force |
20Micro ohms |
13.Capacitor Switching Capacity(Single Bank) |
400A,r.m.s |
MECHANICAL DATA |
1.Contact Force from Atmospheric Pressure |
19.8kgF |
MECHANICAL REQUIREMENTS(REF. VCB) |
1.Contact Stroke |
9±1 mm |
2.Opening Speed(average of 75 contact gap) |
0.9-1.3m/Sec |
3.Maximum Overtravel During Opening |
2mm |
4.Maximun Rebound During Opening |
2mm |
5.Closing Speed(average of last 30% contact gap) |
0.4-0.8m/Sec |
6.Maximum Contact Bounse Duration(with maximum 2 bounces) |
0.002Sec |
7.Rated Contact Compressive Force |
390-450kgF |
LIFE (ESTIMATED) |
1.Electrical Life at Rated Normal Current |
30,000Operations |
2.Electrical Life at Rated Short Circuit Current |
50Operations |
3.Mechanical Life |
30,000Operations |
4.Contact Erosion Limit |
3mm |
5.Shelf Life |
30Years |
Product Image
Img 1
Send Inquiry to this Member
Related Products of this Company
This member assumes full responsibility for the content of this listing. DIYTrade accepts no responsibility whatsoever in respect of such content.
To report fraudulent or illegal content, please
click here.
China Suppliers Quick Searching:
,