Model: | SU1-20KVA |
---|---|
Brand: | Prostar |
Origin: | Made In China |
Category: | Electronics & Electricity / Power Supply & Distribution / UPS |
Label: | UPS , UPS on line , power supply |
Price: |
-
|
Min. Order: | 20 pc |
Live Chat: | Last Online:08 Jun, 2007 |
SU1K~20K(Single in and single out) | |||||||
Mode: | SU1K | SU2K | SU3K | SU6K | SU10K | SU15K | SU20K |
Capacity(VA/W) | 1K/0.8K | 2K/1.6K | 3K/2.4K | 6K/4.8K | 10K/8K | 15K/12K | 20K/16K |
Voltage | Single phase with two Lines + ground wire ,220V±25% | ||||||
48V | 96V/192V | 192V | |||||
Noise | ≤52dB(distance | ≤60dB(distance | |||||
Size: | 530×264×592 | 630×343×725 | |||||
(W×D×Hmm) | |||||||
Weight(Kg) | 30 | 40 | 45 | 60 | 105 | 130 | 160 |
(excluding the battery) |
Common parameters | ||
Input | Frequency | 50Hz /60Hz ± 10% |
Power actor | ≥95% | |
Output | Voltage | 220V± 0.5%<}0{><0} |
Voltage regulation | Stable voltage±1%,dynamic oltage±2%,(0-100% load fluctuation20ms) | |
Frequency stableness | 50Hz /60Hz ± 0. 5% | |
Frequency torsion rate | Less than 1Hz / second | |
Instant load status | ± 0.4%(100% instant load fluctuation) | |
Harmonic distortion | For linear load, less than 3%(full load),total rectifying harmonics is lass than 5% | |
Overload capacitance | 150% | |
Wave form | Sine wave | |
efficiency | Input AC to output AC | Above 95% |
Transfer time | Mains power supply fails or restores | 0 second |
Turns from UPS to BYPASS | Less than 4 ms | |
type | Lead-acid sealed, maintenance-free | |
Charging time | After it is fully charged, it can be filled to 90% of the total Capacity after it is charged for 8 hours. | |
Warning sound | If the main power fails, it buzzes once every 4 seconds. | |
If the battery is low, it buzzes once every 1 second. | ||
If the battery stops discharging, it buzzes continuously. | ||
In fault tatus | Continuously buzzes | |
Automatically shuts down the machine when the battery power is low, it has no fuse switch protection. | ||
Internal Protecting | Overload | After the overload (110~150%) lasts for 10 seconds ,it automatically jumps to BYPASS. It can automatically restore normal state. |
device LCD | Temperature is too high | If the internal temperature of the UPS> Automatically jump to BYPASS. |
panel | Output short circuit | Limits Current, automatically shuts down the machine, without Fuse switch protection. |