Model: | SXBP |
---|---|
Brand: | sansionpower |
Origin: | Made In China |
Category: | Electronics & Electricity / Other Electrical & Electronic |
Label: | test system , resonant test , Variable Frequency |
Price: |
US $100
/ pc
|
Min. Order: | 1 pc |
Live Chat: | Last Online:31 Oct, 2017 |
Test Object and Requirement
The system is specially designed for AC withstand voltage test for below items, with below specifications and requirements.
Test Object |
Specifications |
Test Frequency |
Test Voltage |
Test Time |
Power cable |
170kV/2000mm2/10km Capacitance ≤2μF |
30-300Hz |
150kV |
15 mins |
Power cable |
400kV/2000mm2/5km Capacitance ≤0.6μF
|
30-300Hz |
220kV |
15 mins |
GIS |
400kV and below Capacitance ≤0.02μF |
30-300Hz |
Max. 750kV |
|
Capacity Determination of the equipment:
4pcs Reactors will be designed, each reactor is 2500 kVA/150kV. Capacity amount is 10000kVA.
Determination:
1) When to do AC withstand voltage testing on 170kV 2000mm2 10kM power cable.
Using 4pcs reactors in paralleled.
Output 150kV/66.6A, testing current is calculated as below:
I=U×103×ω×C×10-6=66A (U:150kV,C:2uF,ω=2πf (f=35Hz))
2) When to do AC withstand voltage testing on 400kV 2000mm2 5kM power cable,
Using 2pcs reactors in series and then these two groups in paralleled.
Output 300kV/33.3A, testing current is calculated as below:
I=U×103×ω×C×10-6=29A (U:220kV,C:0.6uF,ω=2πf (f=35Hz))
3) When to do AC withstand voltage testing on 400kV and below voltage degree GIS and etc. equipment, the capacitance is 0.02 uF,
Using 4pcs reactors in series, output 600kVA/16.6A, resonant frequency and testing current is calculated as below:
I=U×103×ω×C×10-6=3.3A (U:512kV,C:0.02uF,ω=2πf (f=50Hz))
REACTORS
TEST OBJECT |
Testing Voltage (kV) |
REACTOR 2500KVA/150kV |
OUTPUT VOLTAGE OF EXCITING TRANSFORMER |
170KV Power Cable |
150 |
4 pcs reactors in paralleled |
7.5KV |
400KV Power Cable |
220 |
2 pcs reactors in series, then two groups in parralled |
15kV |
400kV GIS |
512 |
4 pcs in series |
30kV |