Home > Products > Electronics & Electricity > Power Supply & Distribution > UPS

LF 3phase 10-200kVA No Break 1LF 3phase 10-200kVA No Break 2LF 3phase 10-200kVA No Break 3LF 3phase 10-200kVA No Break 4LF 3phase 10-200kVA No Break 5
  • LF 3phase 10-200kVA No Break 1
  • LF 3phase 10-200kVA No Break 2
  • LF 3phase 10-200kVA No Break 3
  • LF 3phase 10-200kVA No Break 4
  • LF 3phase 10-200kVA No Break 5

LF 3phase 10-200kVA No Break

Model:PVA2
Brand:HRD/OEM
Origin:Made In China
Category:Electronics & Electricity / Power Supply & Distribution / UPS
Label:UPS , no break , online UPS
Price: US $1750 / pc
Min. Order:1 pc
Inquire Now Add to Basket

Member Information

Detail

Shenzhen HRD Science & Technology Co.,Ltd

Free MemberGuang Dong - China
Live Chat:Last Online:26 Jan, 2016

Product Description

UPS truck sale LF 3phase 10-200kVA No Break for 190/208/220 VAC

low frequency UPS

 

Quality power supply :
 • HRD PV(II)series is an On-Line double conversion (VFI) UPS with isolation output transformer, unit capacity from 10kVAto 400kVA. It is immune to the interferences on the electric power supply line as it has special input and output filters. World leading DSP technology, with high speed DSP processor are adopted to guarantee system’s high stability and giving stable output power supply for all kinds of harsh load.

 

Maximum Reliablity

 • MTBF >200,000h.
 • The advanced DSP technology appliance considerably improves reliability, since a reduction in electronic components lowers the likelihood of breakdowns. Digital control is provided by the microprocessor that, in the PV(II) series controls all the internal parameters, thus increasing reliability and performance. In parallel connections, digital control ensures balance of the currents, which generally change over time due to phenomena such as vibrationsand temperature, between the UPS units and the exchange of information with no need for manual tuning. PV(II) has been designed so that it can be connected in parallel even after the installation of the first unit. The power availability can be increased thanks to various configurations available such as the parallel configuration, the Dual Bus function and the Dynamic Dual Bus system.

 

High Speed DSP Processor:

 • Ensuring the operation more faster and more stable

 

Ouput 100% Unbalance Load

 • The UPS can accept 3phase 100% unbalance load to satisfy kinds of load configuration.

 

UPS For Industrial Loads

 PV(II) series with its strong overload capability, output galvanic isolation and low harmonic current distortion, is the ideal solution for industrial applications.

Thanks to the high battery current, PV(II) Series is suitable to work with large battery banks as it can guarantee recharging in 10 hours as recommended by the battery manufacturer.

 

Operating Flexibility:

 • All power ratings of the PV(II) series can also be used as Frequency Converters 50 to 60 Hz and vice versa.

 

Optimal battery management (ABM)includes:

  • Periodic battery test, and automatically transfer between boost charging and float charging to extend battery lifespan
  • Automatically adjusting the battery charging current according to battery capacity
  • Recharge temperature compensation (optional)
  • Remaining  back up time display

 

Maximum Safefy For Personnel

 • The back feed protection device prevents any voltage back feed in the upstream distribution board, thus ensuring the safety of the maintenance personnel.

 

Advanced Parallel
 • Maximum parallel up to 8 units and share the common battery pack.10-80kVAparallel  can be with parallel card only ; 100kVA-200kVA, parallel card  with  weaver reactance and different capacity UPS can be also be parallel;

 

Dynanic Dual Bus System
 • Two independent systems set in Dual Bus Configuration can be merged together at any time for system expansion or maintenance. This provides a lot of flexibility in your installation in case of maintenance or when it is necessary to change the redundancy level of both systems.

 

Specification of N+X Parallel 100kva ups price in egypt:

 

Model

PVA3310II

PVA3315II

PVA3320II

PVA3330II

PVA3340II

PVA3360II

PVA3380II

Capacity

10kVA

15kVA

20kVA

30kVA

40kVA

60kVA

80kVA

system

Output PF 

0.8 (lag)

System efficiency  (inverter mode)

92%(@100% load) ;90% @50%load;

System efficiency  (ECO mode)

98%(@100%load)

Maximum leakage current

100(mA)

MTBF

Above 200,000hours

Dry contact

 Standard: 3 types signal(BAT. low,battery mode,bypass /failure);

Optional:14 dry contact ; output: 12Vdc 80mA

Communication interface

Standard RS232,optional: RS485 / MODBUS

Operation temperature

0 ~ 40 °C

Humidity

95 % (non-condense)

Cooling

Forced air(speed varying according to load percent)

Max. altitude

Within 1000m(every 100increase,capacity decrease -1%),Maximum 4000m

Noise (dB)

52 ~ 58

IP protection

(EN 60529)

IP20

Input/output way

Bottom /rear

Safety standard

safety:GB4943 ,EN 50091-1;EMI:GB7260.2,GB/T 17626.2~5EMC, EN 50091-2

Physical

W *D*H(mm)

600*600*1280

800*800*1480

Weight(kg)

230

250

260

305

345

500

560

AC input

Rated voltage

 190/208/220Vac (Line-Line) Three-phase three-wire

Input voltage range

± 15 %- ± 25 % adjustable)

Rate frequency

50 / 60 Hz  auto-sense

Frequency range

50/60Hz+/-5Hz

Input soft start function

0 - 100%,10-300s(settable)

Input power factor

Reachable 0.99(plus harmonic filter)

Input current harmonic component(THDi )

Can <5%(plus harmonic filter)

Max. input current [A]

18

27

36

54

72

108

144

The output characteristic of the rectifier

Maintain the voltage (20°C)

Battery type1 and 2 :V =435Vdc (2.266 x el.)

Battery type 3 :V =424Vdc (2.21 x el.)

 Battery type 0:the voltage value between type 1and 2,

Voltage regulating range: V =400~460Vdc

Charging voltage (20°C)

Battery type1 and 2 :V (%recharging<95%) = 445Vdc (2.32 x el.)

Battery type 3 :V (%recharging<95%) = 460Vdc (2.4 x el.)

Battery type 0: the voltage value between type 1and 2,

Voltage regulating range: V =400~460Vdc

The highest charging voltage

445V

The charger output voltage regulation accuracy

1%

DC ripple voltage component

≤1%

Battery

Unit number(rated voltage)

384Vdc(360-384v,selectable)

Charging current settings

0.1C(battery capacity)

The battery discharge end voltage

Battery type 1,2 and 3:no-load discharge current,V min=346 [V dc]

Battery type 1,2 and 3:output current =Ah capacity,V min=316 [V dc]

Battery type 1,2 and 3:output current >Ah capacity,V min=306 [V dc]

Battery type 0: the factory set the default values,V min=320 [V dc]  

Regulating range: V min =300~360[V dc]

Inverter output

Rated capacity  [kVA]

10

15

20

30

40

60

80

Rated power  [KW]

8

12

16

24

32

48

64

Rated voltage  [V]

 190/208/220Vac(Line to Line),   three-phase four-wire

Rated current  [A]

24

36

48

72

96

144

192

Phase voltage setting

100 ~ 127 V (control board)

Peak factor

3:1

Waveform

Sine wave

Voltage phase shift (degrees)       100% balanced load

± 1'

Voltage phase shift (degrees)

100% unbalanced load

± 2'

Phase voltage difference         100% balance load

± 1 %

Phase voltage difference         100% unbalanced load

± 3 %

Total harmonic content(THD v)                                100% linear load

<2%

Total harmonic content(THD v)                               100% non-linear load

<5%

Steady-state voltage stability

± 1 %

Transient voltage response

± 5 % within 10ms

Rated frequency

Same as input

Frequency stability

When asynchronous,± 0.5 %;synchronization,± 2 %

(can be set to ± 1~5 %,by the panel operation)

Overload

  600’ / 10’ / 1’ (110/125/150% rated current)

Short circuit 0.1s

Double input

Inverter efficiency           (load 100%)

98%

 

 

 

Packaging & Shipping

N+X Parallel 100kva ups price in egypt.jpg 

 

Company Information

 Date Center Luminous UPS Prices in Egypt HRD company.jpg

 

Date Center Luminous UPS Prices in Egypt 5.jpg

company product line.png

 

Certifications

 N+X Parallel 100kva ups price in egypt1.jpg

Our Services

1. 1.5% spare parts of quantity with delivered with UPS

2. OEM/ODM: allowing to use the customer logo based on order quantity

3. Warranty for 2 years from shipment date

4.If any part fails within warranty and needs repairing or replacing, please send part or board back to us (you pay for the freight), Or you provide the exact details information as per our requriment, and we offer you free spare parts and send to you( you pay the freight fee)

 

Three Phase UPS Medical Equipment New York2.jpg

 

FAQ

 Three Phase Rectifier Bridge UPS Made in China.jpg

 

 

 

Contact

Mona Lai | Shenzhen HRD Science & Technology Co.,Ltd | (Shenzhen MOTU Power Supply Co.,Ltd) 

Mobile/Whatsapp: +86-18565620560 | Skype: mona.lai28

Tel: +86-755-81737467 | Fax: +86-755-81737252

E-mail: 1231.png | Web: www.hrdups.com 

Add: 4th floor No.7 building,Changxing High-Tech Industrial Park,Shajing Town,Bao'an District Shenzhen China-PC518104


Product Image

LF 3phase 10-200kVA No Break 1
Img 1
LF 3phase 10-200kVA No Break 2
Img 2
LF 3phase 10-200kVA No Break 3
Img 3
LF 3phase 10-200kVA No Break 4
Img 4
LF 3phase 10-200kVA No Break 5
Img 5

Send Inquiry to this Member

Shenzhen HRD Science & Technology Co.,Ltd

4th floor No.7 building,Changxing High-Tech Industrial Park,Shajing Town,Bao'an District Shenzhen China

Phone:
86-0755-81737467
Fax:
86-0755-81737252
Contact:
Mona (sale)
Mobile:
18565620560

Related Products of this Company

This member assumes full responsibility for the content of this listing. DIYTrade accepts no responsibility whatsoever in respect of such content.
To report fraudulent or illegal content, please click here.

China Suppliers Quick Searching:

UPS Made In China Products

,  

UPS China Suppliers and China Manufacturers