Product Description
Genset | Prime Power (kva) | 120 |
Standby Power (kva) | 138 |
Rated Voltage (Volt) | 400/230 (adjustable) |
Rated Current (Amp) | 182 |
Rated Frequency (Hz) | 50 |
Rated Speed (r/min) | 1500 |
Cooling Method | Closed cycle water-cooled with the fan |
Dimension (L*W*H) mm. | 2900*1100*1600 | 2300*800*1500 |
Weight (kg) | 1900 | 1200 |
| Engine Brand | CUMMINS |
Diesel Engine | Engine Model | 6BTA5.9-G2 |
Engine Structure | 6 cylinders in-line,4 stroke,turbocharged, water-cooled. |
Bore*Stroke (mm) | 102*120 |
Compression Ratio | 17.5:1 |
Displacement (L) | 5.9 |
Lube Capacity (L) | 12.1 |
Fuel Consumption (L/h) | ≤25 |
Lube Consumption (L/h) | 0.5% |
Rotating Speed (r/min) | 1500 |
Type of Governor | Electronic |
Starting Mode | Electric start by 24V battery |
| Alternator Brand | ENGGA |
Alternator | Alternator Model | EG225L-100N |
Features | Brushless, self-excitation, AVR regulation |
Protection Grade | IP22 |
Insulation Class | Class H |
Steady Voltage Regulation | ≤±1% |
Instant Voltage Ragulation | -15%~+20% |
Voltage Regulation Scope | >10% |
Power Factor | 0.8 Lagging |
Connection Type | 3 phase 4 wire,Y type |
Controller | Model | Harsen GU320B |
| | | | | | |
*Function Of Controller | | | | | |
Bitmap 1) Chinese/English menu for your choice, large LCD display., 2) LED indicator is used for indicating the controller running mode and Genset running status, and LCD display measuring parameter and status; 3) low oil pressure,high temperature,overspeed,charge fail, fail to start,emergency stop etc. alarm and protection function; 4) Auto/manual start. |
|
|
|
|
|
Product Image
Img 1