Model: | UK2.5B |
---|---|
Brand: | phoenix contact |
Origin: | Made In China |
Category: | Electronics & Electricity / Electronic Components / Terminal |
Label: | terminal block , terminal , phoenix contact |
Price: |
US $0.3
/ pc
|
Min. Order: | 50 pc |
Feed-through terminal block - UK 2,5 B - 3001035
Feed-through terminal block, Connection method: Screw connection, Number of connections: 2, Cross section: 0.2 mm² - 4 mm², AWG: 24 - 12, Width: 6.2 mm, Color: gray, Mounting type: NS 35/7,5, NS 35/15
General
Number of levels | 1 |
---|---|
Number of connections | 2 |
Potentials | 1 |
Nominal cross section | 2.5 mm² |
Color | gray |
Insulating material | PA |
Flammability rating according to UL 94 | V0 |
Rated surge voltage | 8 kV |
Degree of pollution | 3 |
Overvoltage category | III |
Insulating material group | I |
Maximum power dissipation for nominal condition | 0.77 W |
Nominal current IN | 24 A |
Nominal voltage UN | 690 V |
Open side panel | Yes |
Shock protection test specification | IEC 60529:2001-02 |
Back of the hand protection | guaranteed |
Finger protection | guaranteed |
Result of surge voltage test | Test passed |
Surge voltage test setpoint | 9.8 kV |
Result of power-frequency withstand voltage test | Test passed |
Power frequency withstand voltage setpoint | 1.89 kV |
Result of the test for mechanical stability of terminal points (5 x conductor connection) | Test passed |
Result of bending test | Test passed |
Bending test rotation speed | 10 rpm |
Bending test turns | 135 |
Bending test conductor cross section/weight | 0.2 mm² / 0.2 kg |
2.5 mm² / 0.7 kg | |
4 mm² / 0.9 kg | |
Tensile test result | Test passed |
Conductor cross section tensile test | 0.2 mm² |
Tractive force setpoint | 10 N |
Conductor cross section tensile test | 2.5 mm² |
Tractive force setpoint | 50 N |
Conductor cross section tensile test | 4 mm² |
Tractive force setpoint | 60 N |
Result of tight fit on support | Test passed |
Tight fit on carrier | NS 32/NS 35 |
Setpoint | 1 N |
Result of voltage-drop test | Test passed |
Requirements, voltage drop | ≤ 3.2 mV |
Result of temperature-rise test | Test passed |
Short circuit stability result | Test passed |
Conductor cross section short circuit testing | 2.5 mm² |
Short-time current | 0.3 kA |
Conductor cross section short circuit testing | 4 mm² |
Short-time current | 0.48 kA |
Result of thermal test | Test passed |
Proof of thermal characteristics (needle flame) effective duration | 30 s |
Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 130 °C |
Static insulating material application in cold | -60 °C |
Behavior in fire for rail vehicles (DIN 5510-2) | Test passed |
Flame test method (DIN EN 60695-11-10) | V0 |
Oxygen index (DIN EN ISO 4589-2) | > 32 % |
NF F16-101, NF F10-102 Class I | 2 |
NF F16-101, NF F10-102 Class F | 2 |
Surface flammability NFPA 130 (ASTM E 162) | passed |
Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
Smoke gas toxicity NFPA 130 (SMP 800C) | passed |
Calorimetric heat release NFPA 130 (ASTM E 1354) | 28 MJ/kg |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
Payment Terms: | TT/DP/DA |
---|---|