PW series 3 phase is a high end uninterruptible power supply, which has adopted the world leading electrical and electronic technology to improve performance with super high reliability MTBF more than 200,000h.
Main features:
1.Three phase in and out system 380/400/415V or 190/208/220VAC, 50/60HZ, complete digital control technology with three fast DSPs including the IGBT rectifier, inverter, charger, discharger.
2. True online double conversion with strong output load capacity, output PF0.9
3.High input power factor, green and energy-saving: Input with PFC and input PF of the whole UPS up to 0.99, THDi less than 2%
4.Wide range of input voltage and frequency: 40-70HZ
5. AC and bypass from separate input AC source is supportable
6. Comprehensive protection measures: Surge Protection, short circuit protection, and other protection to ensure the reliability of UPS system; IGBT and SCR adopt the advanced EUPEC power module;
7. Similar modular design; Main board of each phase are designed like rack for easy assembling and maintenance,Inbuilt battery pack plug-in design for easy use
8. Intelligent battery management :ABM Automatic temperature compensation to extremely extend battery life by 30% and minimize the maintaining work; Online detecting battery status; Charging current settable from LCD SCREEN 1-40A battery inverse connection protection, back up time display, Periodic self-test battery, detecting the battery problems timely;
9. Cold start and AC start Function.
10. Superior network monitoring capabilities : Communication port RS232, RS485, dry contact and so on connecting with computer, SNMP optional.
11. Easy-maintenance design a. full front maintenance design. b. Modular design class, convenient and easy site maintenance. c. With manual maintain bypass. d. Battery replacement without disrupting the UPS running e. Historical records 1000 items
12 Advanced parralel technology and LCD display
Technical specification:
Model |
PW3360 |
PW3380 |
PW33100 |
PW33120 |
||||
Rating Power |
60Kva/54Kw |
80Kva/72Kw |
100Kva/90Kw |
120Kva/108Kw |
||||
AC Input |
||||||||
Rated voltage |
380/400/415Vac(Line-Line) |
|||||||
Input connection |
3phase +N+PE |
|||||||
Power factor |
Above 0.99 |
|||||||
THDi |
Less 2% |
|||||||
Voltage range |
-40%~+25% |
|||||||
Frequency |
40-70Hz |
|||||||
Bypass |
+/- 15%(settable) |
|||||||
Output |
||||||||
Power factor |
0.9 (lag) |
|||||||
voltage precision |
380/400/415Vac±0.5% |
|||||||
Dynamical voltage transient |
Less 5% ( 0~100% load step) |
|||||||
THDU |
THD less 0.6%( linear load ),3%(non-linear load) |
|||||||
Crest Factor |
3:1 |
|||||||
Frequency tracking range
|
50/60Hz±3Hz |
|||||||
Output Frequency precision |
±0.05%(Battery mode) , ±3hz(Line mode) |
|||||||
phase displacement |
120±0.5°(Balance or imbalance load ) |
|||||||
Voltage unbalance |
+/-3%( 100% unbalance load) |
|||||||
Frequency tracking rate |
Less 1Hz/s |
|||||||
Overload capability |
110%, 1 hour; 110%<load<125%, transfer to bypass after 10 mins; |
|||||||
125%<load<150%, transfer to bypass after 1min; above 150%, transfer to bypass after 200ms. |
||||||||
Bypass overload |
Below125% long time operation 125%<Load<150%,10mins;above 150% 1S |
|||||||
System |
||||||||
System efficiency |
Above 94%(Line and battery mode) |
|||||||
98%(ECO mode) |
||||||||
Display |
Touch screen LCD+LED |
|||||||
EMC |
IEC62040-2 |
|||||||
IEC61000-4-2 (ESD) |
||||||||
IEC61000-4-3 (RS) |
||||||||
IEC6100-4-4 (EFT) |
||||||||
IEC6100-4-5 (Surge) |
||||||||
Noise (1m) |
50- 60dB |
|||||||
Insulating resistance |
Above 2M (500VDC) |
|||||||
Insulating intensity |
(input, output to PE) 2820Vdc, leakage current lower than 3.5mA, no flashover in 1min |
|||||||
Surge protection |
Meet the requirement of IEC60664-1class,endure surge of 1.2/50us+8/20us higher than 6KV/3KA |
|||||||
IP class |
IP20 |
|||||||
Battery configuration |
||||||||
Installation(dc) |
+/-216Vdc( +/-168/192/216/240Vdc ,settable from LCD screen) |
|||||||
Battery type |
Free Maintenance Lead Acid (Gel battery or Ni-Cd) |
|||||||
Connection |
Bottom cable connection in front |
|||||||
Charger |
10-40A( settable from LCD screen) |
|||||||
Physical |
||||||||
Unit Dimension (UPS) |
600×850×1680 MM (W*D*H) |
735×850×1680 MM (W*D*H) |
||||||
Unit Dimension (Packing) |
954×704×1857 MM (W*D*H) |
954×839×1857 MM (W*D*H) |
||||||
Weight N/G (KG) |
240/280 |
260/300 |
320/360 |
340/380 |