| Operating Condition |
| 1. Operating Temperature Range: (-20~80)℃ |
| 2. Storage Temperature Range: (-40~100)℃ |
| 3. Factory set: 25℃±5℃ |
| Electric Index |
| 1. Voltage: 230±2V |
| 2. Voltage Steady Range: ±1V |
| 3. Starting Excitation Voltage: ≥1.5V |
| 4. Loading Capacity: With 110% loading, the regulator can work normally. |
| 5. Output Voltage Steady on hot and cool condition ≤2V |
| 6. Temperature float on Output Voltage≤2V |
| Protection Function |
| 1. Short Circuit Protection on generator rotor excitation. |
| 2. Short Circuit Protection on loading output. |
| 3.Short Circuit Protection between primary and secondary winding |
| 4.Protection after break down on sampling winding |
| Anti-interference Ability |
| Specification for Regulator and fitted generator |
| 1. When Generator Output Voltage is 230V, the Sampling Voltage is 18V |
| 2. During the time from without loading and with loading, the secondary winding voltage is less than 150V |
| 3. During the time from without loading and with loading, the excitation current is less than 2.5A |
| Model Testing |
| 1. Temperature Capacity: Put regulator into 80℃ Oven and then connected outside with Generator by wire and with full loading,after 48 hours continuous operating, the regulator works well. |
| 2. Durability Test: With full loading and continuously operating 250 hours, the regulator can work well. |
| 3. Short Circuit Testing: After the output short circuit, the regulator is not damaged. Testing Method: short for 2 seconds and out for 8 seconds with 200 cycles |
| 4. Shoke Testing |
| 5. Over loading Capacity |
| 6.Output Value of Drift Testing |