with all protection like HP, LP protection, water flow shortage protection, auto-defrosting, anti-freezing, etc
Features:
It can be easily combinated into any size system at the project spot. Maximun 64 units can be connected together for the largest 4224KW capacity.
Adopting flange connection for the water pipe junction between units makes the connection work easier to be finished.
Parameter:
HEAT PUMP LSQ66R4
Heat output/Power consumption at 7/35° kW 69/19
Heat output/Power consumption at 7/45° kW 68/22.5
Heat output/Power consumption at 7/55° kW 67/30.5
Heat output/Power consumption at 2/35° kW 57/19
Heat output/Power consumption at 2/45° kW 56/22.5
Heat output/Power consumption at -7/35° kW 44/18.5
Heat output/Power consumption at -7/45° kW 43/22
Cool output/Power consumption at 35/7° kW 66/23
Power 380-415V/3PH/50Hz
Compressor 4×Scroll
Condenser Brazed plate heat exchanger
Nominal flow heating medium l/s 3.2
Internal pressure drop at nominal flow kPa 25
Air flow m3/h 20000
Nominal output fan W 750x2
Max outgoing heating medium temperature ° 58°
Width mm 2010
Depth mm 980
Height mm 1850
Pipe connector DN100
Weight kg 660